Passive Filter Design To Reduce Electrical Disturbances In The Manufacturing Industry
##plugins.themes.academic_pro.article.main##
Abstract
Industry is one of the economic sectors that plays a role in processing environmental resources into products with higher utility values. This process includes design activities, industrial engineering, and service provision. Matra Abadi Workshop, a manufacturing industry that in its operations produces harmonic currents in the electric power system network, especially in low-order harmonics such as 3rd, 5th, 7th, 9th, and 11th. To reduce the negative impact of harmonics on the power system, the use of passive harmonic filters is required. Among the types of filters used, single tuned filters are a common choice because of their simple construction and effectiveness in reducing certain order harmonics that exceed the IEEE 512–2014 standard limits. This study discusses the implementation of both types of filters in a manufacturing industry environment. The harmonic reduction process is carried out through filter design and testing using Matlab/Simulink software-based simulations. The simulation results show that after the application of passive filters, the harmonic current levels in all load configurations were successfully suppressed to within the IEEE 512–2014 standard limits. The reduction in Total Harmonic Distortion (THDi) after the application of the single tuned filter was recorded in the range of 17.86% to 11.06%. In addition, there was an increase in the power factor from 0.68 before the filter was installed to 0.91 after the installation, which indicates an improvement in the overall power system performance.
##plugins.themes.academic_pro.article.details##

This work is licensed under a Creative Commons Attribution 4.0 International License.
References
[2] B. Kennedy, Power Quality Primer. McGraw-Hill, 2000.
[3] D. Committee, I. Power, and E. Society, “IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems IEEE Power and Energy Society,” vol. 2014, 2014.
[4] S. B. Efe, “Harmonic filter application for an industrial installation,” 2015 13th Int. Conf. Eng. Mod. Electr. Syst. EMES 2015, pp. 31–34, 2015.
[5] C. Banks, M. Awadalla, M. Orner, and A. Mohamed, “Single-tuned Filter Design for Harmonic Mitigation,” no. 3, 2015.
[6] S. Masykur, Analisis Sistem Tenaga Listrik. Medan: USU Press, 2016.
[7] R. Sachan and R. Srivastava, “Performance analysis of fixed shunt passive filters for harmonic mitigation,” Int. Conf. Emerg. Trends Electr. Electron. Sustain. Energy Syst. ICETEESES 2016, pp. 87–90, 2016.
[8] M. F. Arman, “Self-tuning Outp put Passive-Filter For Low L Power DC / AC Inverters.”
[9] Y. Cho and H. Cha, “Single-tuned Passive Harmonic Filter Design Considering Variances of Tuning and Quality Factor,” Int. Counc. Electr. Eng., vol. 1, no. 1, pp. 7–13, 2011.
[10] F. C. D. La Rosa, Harmonics and Power Systems. Distribution Control Systems, Inc., 2006.
[11] L. I. Kovernikova, “Centralized normalization of voltage harmonics in the network with distributed nonlinear load by the third-order filters,” Int. Sch. NONSINUSOIDAL Curr. Compens., pp. 148–151, 2010.